Information in this document is for general purposes only. While we make every effort to ensure accuracy, we make no guarantees and reserves the right to change details without notice. For the latest information, please contact us or visit our website.

Overview

The EH-0200 inverter is an energy storage bidirectional power conversion system designed for the bidirectional energy conversion between batteries and the grid AC power. Its main component is an inverter composed of power electronic components with embedded control software.

  • Three-level topology, up to 99% conversion efficiency, better power quality

  • Integrated cluster-level battery management function, high battery availability

  • Intelligent multi-stage fan speed regulation, wide temperature operation capacity, up to 45 °C no derating.

  • Support constant power, constant current, constant voltage control, with a frequency modulation, VSG, and other functions

  • Support IEC61850 protocol, with millisecond-level responsiveness

  • IP66 protection, outdoor use.

Electrical diagram

Specifications

Battery side - DC

Max. DC voltage

1,500Vdc

Max. DC current

224.5Adc

Battery system voltage range

1,000-1,500Vdc

Grid side - AC

Rated power

200kW

Max. AC power

220kW

Rated grid voltage

690Vac, 3W+PE

Grid voltage range

586.5~759V(settable)

Max. AC current

184.1Aac

Rated grid frequency

50/60Hz

Harmonic (THDi)

<1.5% (100% load)

AC power factor

-1~+1

General

Isolated

No

Max. efficiency

99%

IP protection

IP66

Operation temperature

-40~+60°C

Allowable humidity range

0~100% (no condensation)

Maximum operating altitude

4,000m

Cooling

Temperature controlled forced air cooling

Communication Interface

RS485/CAN/Ethernet

Dimensions(WxDxH)

810×275×845mm

Weight

100kg

Proven performance

Our inverters are based on a proven design from one of the world’s largest solar inverter manufacturers. They are fully certified by TUV according to FINGRID class A to class D for use in installation from 1MW to above 30MW and for 110kV grid connections and support all frequency regulation modes as well as grid forming where required. The inverters have also been fully tested according to ELERING requirements for class A to class D installations.

Response time

From the time of issuance of a Modbus power command to our BESS container controller, it takes the inverters between 100ms and 300ms to reach the required power as measured by external fast meter. This includes power commands from maximal charge power to maximum discharge power. Faster response time are possible via optimization.

Suppliers

The EH-200-HA-M grid inverter was originally developed and is manufactured by SINENG Electric Co. It can be contract manufactured in Taiwan if required. This gives us dual sourcing capabilities and faster deliveries.