PQ and derating curves for EH0200 inverter

Prev Next

EH-0200-CAL-DOC-01-V3

PQ curves and derating for EH0200 inverter

Main parameters

DC Input range

1000~1500Vdc

AC Voltage

690Vac

MAX Power

220kVA @30℃

PQ curves

By default, the PCS operates in active power priority. When required, it can operate on reactive power mode with two options:

Working mode 1:

In this mode, PCS operates in reactive priority mode by default; When scheduling according to "controlled direct reactive power regulation", the maximum reactive power capacity is S=220kVA. After responding to the reactive power Q kVar capacity, the remaining capacity P kW capacity is then used to respond to the active power

Working mode 2:

In this mode PCS operates in reactive priority mode by default;  When conducting constant power factor scheduling according to the "controlled power factor adjustment", it has the following table characteristics.

PQ tables for 20C1600K

Standard table for reactive power and active power limits.

Power factor cosΦ

Active Power MAX. kW

Reactive Power MAX. kVar

1.00

220.00kW

.00kVar

0.95

209.00kW

68.69kVar

0.90

198.00kW

95.90kVar

0.85

187.00kW

115.89kVar

0.80

176.00kW

132.00kVar

0.70

154.00kW

157.11kVar

0.75

165.00kW

145.52kVar

0.65

143.00kW

167.19kVar

0.60

132.00kW

176.00kVar

0.55

121.00kW

183.74kVar

0.50

110.00kW

190.53kVar

0.45

99.00kW

196.47kVar

0.40

88.00kW

201.63kVar

0.35

77.00kW

206.08kVar

0.30

66.00kW

209.87kVar

0.25

55.00kW

213.01kVar

0.20

44.00kW

215.56kVar

0.15

33.00kW

217.51kVar

0.10

22.00kW

218.90kVar

0.05

11.00kW

219.72kVar

0.00

.00kW

220.00kVar

Derating with bus voltage

The battery voltage range that supports the PCS operating at rated power is 1,000– 1,400 Vdc.

The battery voltage range of the 20C2H1600K is 1,075.2–1,363.2 Vdc (cell voltage: 2.8–3.55 Vdc) within this range. The PCS operate at 80% of the rated apparent power at 1500Vdc. If the battery voltage drops below 1,000 Vdc or rises above 1,500 Vdc, the PCS will not operate. The calculation is determined by internal software and hardware design of the R&D department,

and complies with IEC 62477-1 (LVD) and IEC 61000-6-2_6-4 (EMC)

Derating with altitude

The PCS is capable of operating at 110% of the rated apparent power at altitudes from 0 to

3000m, 100% of the rated apparent power at 4000m.

The calculation is determined by internal software and hardware design of the R&D department, and complies with IEC 62477-1 (LVD) and IEC 61000-6-2_6-4 (EMC).

Derating with temperature

The PCS is capable of operating at 110% of the rated apparent power at-30℃-35℃,

100% of the rated apparent power at 45℃.

The calculation is determined by internal software and hardware design of the R&D department,

and complies with IEC 62477-1 (LVD) and IEC 61000-6-2_6-4 (EMC)