EH0200 inverter protection settings

Prev Next

EH0200-CAL-DOC_v3

Inverter protection settings

Disclaimer

Information in this document is for general purposes only. While we make every effort to ensure accuracy, we make no guarantees and reserves the right to change details without notice. For the latest information, please contact us or visit our website.

Primary protection functions

Over/Under voltage Protection

Protection Condition

Protection Time

Protection Action

Recovery Time

Ur < 0.2 pu

1 s

Grid-connected contactor trips, DC switch trips, converter disconnects from grid, startup prohibited

Flexible configuration possible; settings modification (0.01–7200 s configurable)

0.2 pu ≤ Ur < 0.9 pu

5 s

Same as above

same as above

0.9 pu ≤ Ur < 1.1 pu

Long-term operation

1.1 pu ≤ U < 1.25 pu

20 s

Grid-tie contactor trips, DC switch trips, converter disconnects from grid, startup prohibited

Flexible configuration possible; settings modification (0.01–7200 s configurable)

1.25 pu ≤ U < 1.3 pu

2 s

Same as above

same as above

1.3 pu ≤ Ur

800 ms

Same as above

same as above

Over/Under frequency

Protection Condition

Protection Time

Protection Action

Recovery Time

f ≤ 46 Hz

200 ms

Grid-tie contactor trips, DC switch trips, converter disconnects from grid, startup prohibited

Flexible configuration available in background; settings modification (0.01–7200 s configurable)

46 Hz < f ≤ 53 Hz

Continuous operation

f > 53 Hz

200 ms

Grid-tie contactor trips, DC switch trips, converter disconnects from grid, startup prohibited

AC Over current

Protection Condition

Protection Time

Protection Action

Recovery Time

IRMS Max > 1.28 pu

30 s

Grid-tie contactor tripped, DC switch tripped, converter

disconnect from grid, and startup is prohibited

15 min

IRMS Max > 1.3 pu

15 s

Grid voltage imbalance

Protection Condition

Protection Time

Protection Action

Recovery Time

Difference in line voltage RMS < 0

Power-on not permitted

5 s

Reverse Grid Phase Sequence

Protection Condition

Protection Time

Protection Action

Recovery Time

Reverse grid phase sequence

1 s

Power-on prohibited

5 s

Main Phase Loss

Protection Condition

Protection Time

Protection Action

Recovery Time

Main phase loss fault

5 s

Power-on prohibited

10 s

Anti Islanding

Protection Condition

Protection Time

Protection Action

Recovery Time

Powered by grid connected to converter → Power interruption

2 s

Grid-tie contactor opens, DC switch opens, converter disconnects from grid, and restart is prohibited

2 s