3.1 Battery system
3.1.1 Battery pack

Figure 3-1 Battery PACK
Table 3-1 Battery pack technical data sheet
NO | Item | Parameter | |
1 | Battery PACK | Nominal capacity | 48.23kWh |
Nominal voltage | 153.6V | ||
Voltage range (V) | 134.4~170.4 (CELL:2.8~3.55V ) | ||
Series and parallel mode of cell | 1P48S | ||
Cell shape | Square | ||
Cell Capacity | 314Ah | ||
Cell rated voltage | 3.2V | ||
Cell voltage range | 2.8V-3.55V | ||
Maximum cell discharge rate | 0.5C | ||
Number of cells | 48 | ||
2 | BMU | Voltage Monitoring Period | 200ms |
Balancing Current | Active balancing, Max 2A | ||
Cell Voltage Measurement Range | 1~4.95 V | ||
Cell Temperature Measurement Accuracy | ±2℃ | ||
Temperature Measurement Period | 3s | ||
Voltage Measurement Accuracy | ±5mV | ||
protection parameter | over-temperature protection(<45℃), Low temperature protection (>0℃), over-current protection(250A/1s) , short-circuit protection (500A/10ms) | ||
3 | weight | Battery PACK | 305kg±8kg |
4 | size | Battery PACK(W×D×H): | 780(W)*1095.4(D)* 238.5(H)mm |
Table 3-2 Ports on battery pack explain

Ports on the battery pack | Position | Label | Definition |
|---|---|---|---|
Secondary terminals | COMM:1 | ADDR | Battery module BMU address code assignment |
COMM:2 | CANH | CAN communication of battery module Internal battery management unit BMU H | |
COMM:3 | CANL | CAN communication of battery module Internal battery management unit BMU L | |
COMM:4 | 24V- | Battery module Internal battery management unit DC24V- of the BMU | |
COMM:5 | 24V+ | Battery module Internal battery management unit DC24V+ of the BMU | |
Primary terminals | 1 | B+ | Battery PACK positive pole |
м | B- | Battery PACK negative pole |
3.1.2 Battery string

Figure 3-2 LS385-8LP48 Battery string layout
Table 3-3 LS385-8LP48 Battery String Configuration Table
NO. | Item | Specification | Qty | Unit |
|---|---|---|---|---|
1 | 20C1600K | Battery string | 8 | string |
Each battery string (battery cluster) contains
1 | Battery pack | Internal integrated battery module, battery pack sampling unit BMU | 8 | set | |
2 | Battery rack | The battery rack is fixed inside the container, and up to 8 battery packs | 1 | set | |
3.2 High voltage unit
3.2.1 High-voltage unit characteristics

Figure 3-3 High voltage unit
The unit has the ability to disconnect the high-voltage unit is the and control of the battery string from the main system. The details are as follows:
· The power circuit uses contactors, fuses and isolation switch integrated to protect the battery string reliably.
· The unit is also CMU integrated. CMU, as the second-level BMS to collect the data from each cell management unit, BMU, realizes current monitoring and protection of the whole string battery and ensures in-time communication.
· The power supply control in the unit adopts a redundant design of the AC-DC power supply, which supports the black start of the system.
Using reliability is balanced with speed to optimize communication, the important information is uploaded by Modbus.
Table 3-4 High-voltage unit technical data table
No. | Item | Specification | |
|---|---|---|---|
1 | Basic parameter | Working voltage | 220V AC |
Working temperature | -20℃~55℃ | ||
Weight | 30kg | ||
Monitoring parameter | Battery string voltage and current | ||
Function | Contactor control, short circuit protection | ||
Communication mode | CAN/TCP | ||
| DC24V: Battery string DC24V power indicator; QF6n: Battery string DC circuit breaker; Size (W x H x D, mm): 800×240×750. | ||
Table 3-5 Ports on the high-voltage unit definition
Ports | Symbol | Specification | ||
|---|---|---|---|---|
Power port | PCS + | Connect to the positive terminal DC side of PCS | ||
PCS - | Connect to the negative DC side of PCS | |||
B+ | Connect to the positive DC side of XBP8 | |||
B- | Connect to the negative DC side of XBP1 | |||
Control signal port | COMM | COMM:1 | ADDR | Battery module BMU address code assignment |
COMM:2 | CANH | CAN communication of battery module Internal battery management unit BMU H | ||
COMM:3 | CANL | CAN communication of battery module Internal battery management unit BMU L | ||
COMM:4 | 24V- | Battery module Internal battery management unit DC24V- of the BMU | ||
COMM:5 | 24V+ | Battery module Internal battery management unit DC24V+ of the BMU | ||
J1 | J1:1 | L1 | External AC220V power supply ~L | |
J1:2 | N1 | External AC220V power supply ~N | ||
J1:3 | PE | External AC220V power supply ~PE | ||
J2 | J2:1 | L1 | Control box or black start 24V+ | |
J2:2 | N1 | Control box or black start 24V- | ||
J2:3 | L1 | high voltage unit AC220V power supply ~L | ||
J2:4 | N1 | high voltage unit AC220V power supply ~N | ||
LAN | Communicatio n RJ45 network port | |||
3.2.2 High voltage unit fuse

Figure 3-4 High voltage unit fuse position
If the fuse is damaged, it needs to be replaced. The replaced fuse must meet the requirements of Table 3-6
Table 3-6 Specification of high voltage unit fuse
NO. | List | Rated voltage | Rated current | Recommended model and brand |
|---|---|---|---|---|
① | DC fuse | 1500VDC | 3A | HD10R4-3A DC1500V/Deer |
② | DC fuse | 1500VDC | 3A | HD10R4-3A DC1500V/Deer |
③ | DC fuse | 1500VDC | 350A | PV15M-350- H/Bussmann |
3.3 GPC control box
3.3.1 Equipment layout

Figure 3-5 Controller appearance

Figure 3-6 GPC control box equipment distribution
The GPC control box is divided into three layers. The first layer is the door of the control box, on which the touch screen (HMI) device is installed, the second layer is the EMU and PCS connecting plate, and the third layer is the internal device layer of the control box.
The device layer inside the GPC control box is divided into upper, middle and lower layers. The upper layer is the power module (KCPS1), switch (SWT), router (TP) and PLC controller, the middle layer is the system internal power supply and signal terminal block, and the lower layer is the reserved system function signal input/output terminal block and relay switch.

Figure 3-7 GPC control box equipment

Figure 3-8 Router port definition
Table 3-7 Router port description
Port definition | Description |
|---|---|
PWR1/2/3 | Power indicator light Steady on: The power supply is provided by this input Off: The input power is not supplied |
SYS/FAULT | Blinking green: The device is working properly Blinking red: The port is not properly connected Other: The communication is abnormal |
Console | RJ45 port |
WAN | WAN port (EMS or SCADA access) |
WAN/LAN | WAN/LAN port |
LAN | LAN port used by internal devices |

Figure 3-9 Fuse core position of GPC control box
If the fuse is damaged, it needs to be replaced. The replaced fuse must meet the requirements of Table 3-8.
Table 3-8 Specification of fuse core of GPC control box
NO. | List | Rated voltage | Rated current | Recommended model and brand |
|---|---|---|---|---|
① | Fuse core
| 250VDC | 6A | 5*20 /UPUN |

Figure 3-10 HMI touch screen
Table 3-9 GPC control box HMI Touch screen Description
Name | Function |
|---|---|
Touch screen HMI | The 10.7-inch industrial touch screen is selected for the human-computer interaction window if the touch screen is not operated for more than 10 minutes, the LCD screen will enter energy-saving mode automatically. |
HMI is the human-computer interaction window of the whole system. System control, state monitoring and operation parameter setting are all realized through HMI. HMI can be divided into five interfaces according to different functions: Home Page, Environmental Control System (ECS), Control, Status, and System.

Figure 3-11 HMI display menu tree
3.3.2 Features and functions of the GPC control box
· Integrated system visualization window HMI.
· System key information collection, current monitoring of charge/discharge data.
· Data information storage is safe and efficient.
· Automatic recording of events, alert information on the top reminder.
· Topology structure shows system status.
· User rights management at different levels using.
· Support physical network cable transmission and wireless signal transmission.
3.4 Primary distribution box
The primary distribution box is the AC output port of the system and is connected to the power grid through an external transformer cabinet. It contains the primary AC switch of the system and the Wire copper bus bar.

Figure 3-12 Primary distribution box layout
Table 3-10 Primary distribution box layout description
NO. | Description |
|---|---|
① | Converter AC side circuit breaker |
② | AC output bus of the system |
③ | Surge protection device and fuses |
④ | Experimental terminals and Breaker signal conversion terminals |
⑤ | Reserve a location for installing transformers on the customer's site |
⑥ | Grounding copper bar |
After passing through the circuit breaker, the AC output of each group of series converters is combined with the AC busbar in the primary distribution box. The busbar is the AC outlet end of the system, where the external transformer or booster bin is connected to the energy storage system.

Figure 3-13 Copper busbar at AC side of the system

Figure 3-14 Fuse position of distribution box
If the fuse is damaged, it needs to be replaced. The new fuse must meet the requirements of Table 3-11.
Table 3-11 Specification and parameters of fuse in distribution box
NO. | List | Rated voltage | Amperage Rating | Recommended model and brand |
|---|---|---|---|---|
① | Fuse | 1000VDC | 3A | HD10PV-3A |
① | AC fuse | 690VAC | 50A | C22G50/Eaton |
3.5 Distribution box
The distribution box contains power switches for secondary equipment and reserved communication acquisition terminals, which are connected to 400V voltage through the power grid.

Figure 3-15 Distribution box layout
NO. | Symbol | Explain |
|---|---|---|
1 | QFSPD2 | Auxiliary source surge protector |
2 | QF2K | Auxiliary power main breaker |
3 | QFUPS | UPS input power breaker |
4 | QFKC | UPS output power supply |
5 | QFFC | Fire controller power breaker |
6 | QFFCM | Fire controller module power breaker |
7 | QFGPC | GPC power breaker |
8 | QFCH | Liquid cooled cabinet power breaker |
9 | QFA1 | DAC power breaker |
10 | QFA2 | HVAC power breaker |
11 | QFPDU | PDU power |
12 | QFL | Container lighting power |
13 | QFHV1 | 1~4#HVU power |
14 | QFHV2 | 5~8#HVU power |
15 | QF61~QF68 | DC breaker QF61~QF68 |
16 | QF21~QF28 | AC incoming breaker QF21~QF28 |

Figure 3-16 Secondary distribution system diagram

Figure 3-17 Primary distribution system diagram
3.6 Environmental control system
The 20C1600K containerʼs environmental control system includes the air conditioner and liquid Chiller unit. The liquid Chiller unit delivers low-temperature coolant to the copper tube inside the battery pack. The coolant will exchange heat with the cells inside the battery pack, and the heated coolant will return to the liquid Chiller unit. The radiator inside the liquid Chiller unit will release heat into the air outside the container.
The air conditioner is responsible for maintaining the air humidity inside the container. When the humidity reaches the set value, the dehumidification function will be activated.
3.6.1 Liquid Chiller Unit
Product Features:
· Integrated design, saving on-site installation and debugging costs
· Independent dual system design with high control flexibility
· High energy efficiency variable frequency compressor, variable frequency design, efficient and energy-saving
· Stepless speed regulation of compressor and intelligent regulation of cooling capacity
· Intelligent speed regulation of fan, constantly matching with thermal load, efficient and energy-saving
· Select RS485 interface to achieve remote setting and monitoring functions
· Equipped with automatic start function for incoming calls and providing various alarm and protection functions
· Environmentally friendly refrigerant that meets RoHS requirements
· High reliability, 365 days/year uninterrupted operation
· Small size and compact structure

Figure 3-168 Liquid Chiller unit (EMW400HCNC1E)
Liquid Chiller Unit Parameter
Dimensions, Weight & Mounting Method | Unit | Value |
|---|---|---|
Weight | kg | 400 |
Installation Method | Floor Mounted | |
Application environment | Outdoor | |
Environmental protection& performance | ||
Work environment | ℃ | -30 to +55 |
Storage environment | ℃ | -40 to +70 |
Noise level | dB(A) | 75 |
IP protection level | IP X5 | |
Refrigerant | R410A | |
Coolant | 50% Glycol Solution | |
Cooling & Heating Capacity | ||
Cooling capacity@L45/W18 | kW | 40 |
Heating capacity | kW | 12.5 |
Outlet coolant temperature | ℃ | 18 |
Recycled flow | ||
Rated circulating flow | L/min | 400@150kPa |
Power consumption | ||
Cooling input power@L45/W18 | kW | 21 |
Heating input power@Tu=10℃ | kW | 14.0 |
Self-cicling Model (only pump operation) Power | kW | 0.94 |
Max Power Consumption | kW | 23.9 |
Power supply | ||
Rated Voltage | V, Hz | 380-415V ,3~ ,50/60Hz |
Support voltage range | V, Hz | 400±15%V ,3~ ,50/60±3Hz |
Max operating current | A | 58.5 |
3.6.2 Dehumidifying air conditioner
.png?sv=2026-02-06&spr=https&st=2026-07-26T21%3A12%3A31Z&se=2026-07-26T21%3A36%3A31Z&sr=c&sp=r&sig=LOv%2FQHLi92iVmc4RRk%2FA3KEZ1uHdunyQ4mzDS%2FI5WfY%3D)
Figure 3-179 Dehumidifying air conditioner (MC03CDNC1B)
Item | Parameter |
|---|---|
External Dimensions (Height x Width x Depth) | 400×550×70mm |
External Dimensions (Height x Width x Depth) With Flange | 400×595×70mm |
Working Temperature Range | +18 ~ +45ºC |
Drainage Hose | Outer diameter of 10mmPU water pipe |
Refrigerant | R513A |
Rated dehumidification capacity (35℃ 95%RH) | 7L/D |
RoHS Compliant | Yes |
Circulating air flowrate under dehumidification mode | 65m3/h |
Rated dehumidification power (35℃ 95%RH) | 170W |
Maximum running power (45℃ 95%RH@high voltage) | 230W |
Rated operating voltage | 220VAC |
Rated current under dehumidification mode | 0.8A |
Max. current(low voltage) | 1.3A |
Power supply range | 90VAC~264VAC 50/60±3Hz |
3.6.3 Air Conditioner

Figure 3-20 Air conditioner (MC06HDNC1A)
Item | Parameter |
|---|---|
External Dimensions (Height x Width x Depth) | 548×315×170mm |
External Dimensions (Height x Width x Depth) With Flange | 582×352×170mm |
Working Temperature Range | -40 to +25ºC(heating) -15 to +55ºC(refrigeration |
Noise Level | 50dB(A) |
Protection from Dust, Water and Wind Driven Rain | IP X5 |
Refrigerant | R134a |
RoHS Compliant | Yes |
Anti-salt fog grade | C4-M |
Cooling Capacity@L35/L35 | 600W |
Heating Capacity | 500W |
Power Consumption@ L35/L35 | 240W |
Current@L35/L35 | 1.15A |
Internal Aieflow | 120m3/h |
Power Supply Range | 220~240V,50~60 Hz |
Max. Current | 2.3A |
Weight | 17kg |
3.6.4 Temperature and humidity sensor

Figure 3-21 Temperature and humidity sensor
The RH811AD053F temperature and humidity sensor is designed mainly for industrial, commercial and general building of environment monitoring. It is used in so many occasions which need to be examined and controlled.Such as factory workshop, purification room, laboratory, engine room, work and commercial buildings,airport, station,museum, stadium and so on.
Table 3-12 Technical parameter
Item | Parameter |
|---|---|
Manufacturer | Greystone |
Model | RH811AD053F |
Working current | <30mA |
Power Supply | DC12V(9~16V) |
Environmental standard | ROHS |
Measuring range and accuracy | Temperature:-20~80℃,Accuracy≤+1℃,25C Accuracy≤±0.5C |
Humidity:0%~100%,Accuracy<+8%,20%~ 80%,Accuracy≤±4.5%. | |
Working temperature | -20℃~80℃ |
3.6.5 Water immersion sensor
|
|
Figure 3-182 Appearance of water immersion sensor | Figure 3-193 Schematic diagram of triggering action |
Table 3-13 Technical parameter
Item | Parameter |
|---|---|
Manufacturer | Soway |
Model | SF11201-31-K1H1-M8PP04 |
Working temperature | -40℃~+80℃ |
Maximum switching voltage(DC) | 200V |
Maximum switching current(DC) | 500mA |
Minimum breakdown voltage | 230Vdc |
Maximum load current | 1.75A |
Maximum contact impedance | 100mΩ |
Minimum insulation impedance | 106MΩ |
Trigger position D | 31mm |
3.6.6 Gon760 fixed gas detector

Figure 3-204 H2/CO gas detector
The shell of "Gon760" series fixed gas detector is explosion-proof as a whole. The shell is made of stainless steel or aluminum alloy, and the contact surface with the gas adopts a filter screen that does not produce adsorption on the measured gas or a stainless steel sintered explosion-proof filter screen. The audible and visual alarm is made of anti-corrosion and anti-oxidation materials, with explosion-proof structural design.
Table 3-14 Technical parameter
Item | H2/CO gas detector | |
|---|---|---|
Manufacturer | new-force | |
Model | Gon760-H2-200Q | Gon760-CO-200Q |
Detect gas | H2 | CO |
Measuring range | 0-40000ppm | 0-1000ppm |
Resolving power | 10ppm | 1ppm |
Working temperature | -20.0℃~50℃ | |
Power waste | <5W | |
Installation method | Wall mounted | |
3.7 Lighting system
3.7.1 LED lighting

Figure 3-215 20W LED Linear Light
Table 3-15 Technical parameter
Item | |
|---|---|
Manufacturer | SLTMAKS |
Model | STL-020AXX |
Power | 20W |
Input voltage | 100-265VAC 50/60Hz |
LED Brand | 200PCS 2835 SMD |
LED Driver brand | CE Driver |
Lumen | 3,600LM |
Lumen efficiency | 180LM/W |
CRI | >80 |
PF | >0.95 |
Lamp size | 603*62*65 mm |
Angle | 120° |
Housing color | White |
Material | Aluminum + PC |
IP | IP40 (Indoor using) |
Lifespan | >50,000H |
N.W | 5.7KG/PC |
Working Temperature | -37°C~+55°C |
Operating Humidity | <95% |
Storage Temperature | -40°C~+80°C |
Certificates | CE RoHS |
3.8 Emergency button

Figure 3-226 Emergency power off button of energy storage system
Table 3-16 Technical parameter
Item | |
|---|---|
Manufacturer | Schneider |
Model | ZB4-BS844 |
Installation diameter | 22mm |
Mechanical life | 300000 times |
Ambient air temperature for storage | -40 - 70℃ |
Ambient air temperature for operation | -40 - 70℃ |
Product Certification | CCC、CE |
3.9 Fire fighting system
3.9.1 Fire controller

Figure 3-237 Fire controller
Table 3-17 Technical parameter
Item | |
|---|---|
Manufacturer | kentec |
Model | K11031M2 |
Construction | 1.2mm mild sheet steel |
IP rating | IP30 |
Finish | Epoxy powder coated |
Colour-lid&box | BS 00 A 05 grey - fine texture |
Mains supply | 230V AC +10%/-15% (100 Watts maximum) |
Mains supply fuse | 1.6Amp (FL.6A L250V) |
Power supply rating | 3 Amps total including battery charge 28V±2V |
3.9.2 Gas release indicator

Figure 3-248 Photoelectric smoke detector
Table 3-18 Technical parameter
Item | |
Manufacturer | Kentec |
Model | 55000-316 |
Sensitivity | Nominal alarm threshold of 0.15 dB/m obscuration, measured in accordance with EN 54-7 |
Supply voltage | 9V to 33Vdc |
Alarm voltage | 6V to 28V |
Power-up surge current | 115μA at 24V |
Normal alarm current | 52mA at 24V |
Operating temperature | -20℃ to +60℃ |
IP Rating | IP23D |
3.9.3 Temperature Detector

Figure 3-249 Photoelectric smoke detector
Table 3-19 Technical parameter
Manufacturer | Apollo |
Model | 55000-121 |
Supply voltage | 9V to 33V |
Storage temperature | -30℃ to +80℃ |
Supply voltage | 9-33 Vdc |
Alarm voltage | 6V to 28Vdc |
Alarm indicator | Red light emitting diode |
Minimum voltage required to light alarm indicator | 12V |
Humidity (no condensation or icing) | 0% to 95% RH |
Designed to IP Rating | IP54 |
3.9.4 Alarm bell

Figure 3-30 Alarm bell
Table 3-20 Technical parameter
Manufacturer | CLAMBELL |
Model | CBE6-RD-024-EN |
Operating Temperature Range | -25℃ to +70℃ |
Operating Humidity Range | 0.96 |
3.9.5 Acousto-optic alarm

Figure 3-31 Acousto-optic alarm
Table 3-21 Technical parameter
Manufacturer | System sensor |
Model | 958CHL1000 |
Operating Temperature | -20℃ to +70℃ |
Strobe Flash Rate | 1 flash per second |
Operating Voltage Range | 9 to 30V |
Volume Control | High,Medium(-10dB(A));Low(-20dB(A)) |
3.9.6 Fire emergency stop button

Figure 3-262 Fire emergency stop button
When the fire emergency stop button pressed, the fire extinguishing agent release function of the system is closed.
Conventional manual push button with glass breakage, Blue color IP67. Complete with mounting box.
Table 3-22 Technical parameter
Item | |
Manufacturer | KAC |
Model | W3A-Y000SG-K013-66 |
Ingress Protection | IP67 |
Maximum voltage | 30VDC |
Current rating(Switch only) | 2 Amps |
Cable Termination | 0.5-2.5mm2 |
Operating temperature | -25℃ to+70℃ |
Humidity | 93%±3% non-condensing |
3.9.7 Manual switch with emergency start

Figure 3-273 Manual switch with emergency start
Conventional manual button outside of glass break, Yellow. IP67. Complete with mounting box. Translucent "Extinguishant Release".
Table 3-23 Technical parameter
Item | |
Manufacturer | KAC |
Model | W3A-Y000SG-K013-65 |
Ingress Protection | IP67 |
Maximum voltage | 30VDC |
Current rating(Switch only) | 2 Amps |
Cable Termination | 0.5-2.5mm2 |
Operating temperature | -25℃ to+70℃ |
Humidity | 93%±3% non-condensing |
3.9.8 Water Firefighting interface

Figure 3-284 Water Firefighting interface
The Storz system is a hermaphrodite, symmetrical coupling which is connected by two internal lugs. The connection size of the adaptor is determined by the internal dimension between the lugs (the KA distance).
Table 3-24 Technical parameter
Item | |
Model | STORZ65/KA81 |
Material | Light Alloy |
Storz Connection | 65 |
ka (mm- lug distance) | 81 |
3.9.9 Gas release indicator
.png?sv=2026-02-06&spr=https&st=2026-07-26T21%3A12%3A31Z&se=2026-07-26T21%3A36%3A31Z&sr=c&sp=r&sig=LOv%2FQHLi92iVmc4RRk%2FA3KEZ1uHdunyQ4mzDS%2FI5WfY%3D)
Figure 3-295 Gas release indicator
Table 3-25 Technical parameter
Item | |
|---|---|
Manufacturer | Kentec |
Model | K27102 |
Working temperature | -10℃ ~ +40℃ |
Working Humidity | To 95% non-condensing |
Operating voltage | -15V ~ 30VDC |
Power Consumption | 140 milliamps max at 24V DC |
3.9.10 Ventilation system control module

Figure 3-306 Ventilation system control module
The ventilation system control module can interconnect the gas detector and the fire control system controller. When the gas detector detects dangerous gases, the ventilation system control module activates the ventilation system to discharge dangerous gases.
Table 3-26 Technical parameter
Item | |
|---|---|
Manufacturer | NHfire |
Model | F-VENT-M |
Size | 190*150*78mm |
3.9.11 Exhaust device


Figure 3-317 Exhaust device
Table 3-27 Technical parameter
Item | |
|---|---|
Manufacturer | NFfire |
Model | FV0300-230 |
Nominal voltage | 230V AC |
Frequency | 50/60Hz |
Input power | 115W/210W |
Reference speed | 3200 RPM |
Maximum airflow | 1300 CFM |
Operating temperature | -20℃~55℃85%HR |
Storage temperature | -40℃~65℃95%HR |
IP level | IP54 |
Anticorrosive grade | C4/C5 |
3.9.12 Air inlet device


Figure 3-328 Air inlet device
Table 3-28 Technical parameter
Item | |
|---|---|
Manufacturer | NFfire |
Model | FV0300-I |
Nominal voltage | 24V DC |
Input power | 20W |
Operating temperature | -20℃~55℃85%HR |
Storage temperature | -40℃~65℃95%HR |
IP level | IP54 |
3.9.13 Pressure relief device

Figure 3-339 Pressure relief devices
Table 3-29 Technical parameter
Item | |
|---|---|
Manufacturer | NHFIRE |
Model | NH-301-JGV |
Action pressure | Open at 100Pa, close below 70Pa |
Pressure relief area | 0~0.02m2 |
Dimension | 350×150mm |
Installation of pressure relief valve housing
When shipping the container, a sealing plate is used at the outlet of the pressure relief valve to prevent water from entering during transportation.
After the container arrives at the destination, the pressure relief valve sealing plate needs to be removed and the outer cover needs to be installed.

Figure 3-40 Pressure relief valve sealing plate
Operation:
Prepare tools | |
|---|---|
1 | Cross screwdriver |
2 | Waterproof glass adhesive |
3 | 9 M4X16 screws(Also can use the screws removed from the seal plate) |
4 | Shovel |
Step1: Disassemble the pressure relief valve sealing plate.
Use a shovel to remove the glue around the sealing plate, use a cross screwdriver to remove all screws on the sealing plate, and then remove the sealing plate.
|
|
|
Scrape away the glue | Remove the screws | Remove the sealing plate |
Step2: Install the outer cover.
Fix the outer cover to the internal pressure balancer. The side of the outer cover with the mesh holes is located at the bottom.
Align the circular hole on the flange edge of the pressure balancer outer cover with the pre embedded rivet nut on the container, and fix it with M4X16 triple combination screw (the original sealing plate fixing hole is the same as the outer cover fixing hole).
Finally, fill the gap with waterproof glass adhesive around the outer flange edge and screw position, as shown in the following figure.
|
|
The outer cover is fastened to the pressure relief valve, with one side of the mesh located below | Fix the outer cover with screws and fill the gaps with waterproof glass glue. |

Figure 3-41 Pressure relief valve installation cover completed
Note: For more details, please consult the after-sales engineer.
3.10 Water fire fighting
|
|
|

Figure 3-42 Fire fighting system components

Figure 3-343 Location of water firefighting interface
The fire fighting system is designed according to the specification and size of the 20-foot container. The fire extinguishing agent is transported from the fire extinguishing agent cylinder group through the main pipe and branch pipe to the nozzle of the container battery room to achieve the fire extinguishing function.
The system includes gas cylinder, fire extinguishing agent, solenoid valve, pressure feedback device, fire fighting control system, etc.
The fire control system is mainly composed of fire detector (temperature and smoke), audible and visual alarm device, emergency start and stop button, air release indicator, fire controller, etc.
The combustible gas detector is separately configured to detect the concentration of hydrogen and carbon monoxide in the battery room, and the signal is transmitted to BESS. At the same time, the container is equipped with pressure relief device, air inlet and exhaust fan.

Figure 3-354 Fire fighting system action logic
This system has two control modes: automatic and electrical manual. There are two independent detection circuits in each protection area. When the first fire signal is given, an alarm will be issued, indicating the location of the fire and reminding the staff to pay attention. When the first 2 detector also signal fire, automatic fire extinguishing controller began to delay phase (0 to 30 s adjustable), after a time delay, open the solenoid valve, solenoid valve needle start bottle storage cylinder head valve, the fire area fire fighting operations, at the same time receive the feedback signal from the pressure switch alarm controller, control panel discharge indicator; When the alarm controller is in the manual state, the alarm controller only sends out alarm signals and does not output action signals. After the on-duty personnel confirm the fire alarm, press the emergency start button on the alarm control panel or the emergency start and stop button at the entrance of the protection area to start the system and spray fire extinguishing agent.
3.11 Power conversion system
The conversion system can realize the bi-directional energy conversion between the battery and the AC power supply of the grid.
Its core part is an inverter composed of power electronic components and embedded control software.

Figure 3-365 EH-0200-HA-M conversion appearance

Figure 3-376 PCS schematic diagram
Table 3-30 Main parameters and specifications
Item | |
|---|---|
Manufacturer | Paneco |
Model | EH-0200-HA-M |
Output rated power | 200kW |
Maximum output DC current | 224.5A |
Output rated voltage | 690V |
Output operating voltage range | -15%~+10%(Configurable) |
Current waveform distortion | THDi<3% (fully loaded) |
Adjustable range of power factor | -1 to +1 |
DC component | <Output current rating × 0.5% |
Rated frequency | 50/60Hz |
Working temperature | -40~60℃(≥ 45 ℃ derating operation) |
Operating altitude | 4000m(derating above 3000 m) |
Cooling method | Smart air cooling |
Power consumption in standby state | <0.5% Pn |

Figure 3-387 conversion configuration
Table 3-31 Appearance structure of the conversion
SN | Name | SN | Name | SN | Name |
|---|---|---|---|---|---|
1 | AC terminal | 5 | LEDs | 9 | Bottom handle |
2 | Communica tion terminals | 6 | Right cooling fans | 10 | Left air outlet |
3 | DC terminal | 7 | Ground node | 11 | Left cooling fans |
4 | Right air outlet | 8 | Top handle | 12 | Top air outlet |
Table 3-32 LED indicator status description
LED color | State | Explain |
|---|---|---|
Green | Steady on | The conversion is turned on. |
Blinking (1s) | The conversion is not turned on. | |
Off | The conversion is not powered on. | |
Blue | Steady on | The back end is connected and the conversion is a slaver. |
Blinking (1s) | The back end is connected and the conversion is a master. | |
Fast blinking (0.5s) | The back end is not connected and the conversion is a master. | |
Off | The back end is not connected and the conversion is a slaver. | |
Red | Steady on | Device failure |
Blinking (1s) | Equipment alarm | |
Off | There is no alarm or fault. |











